Select a row below to filter reviews.
5.0
Voltage Measurement (DC)
V1, V2, V3, V4 = 0-80VDC
Voltage Measurement Accuracy
+/- 0.1V
Current Measurement (DC)
I1, I2 = 0.1A to 15A (20A Peak) using 12AWG Wire, I3 = +/-10A
I4 Supports External Current Shunts – Input Range +/-25mV
Current Measurement Accuracy
+/- 0.1A
Common Mode Voltage Range
-14V to +80V
Temperature Measurement
T1,T2 = -40C to 125C
Temperature Measurement Type
T2 = Embedded, T1 = External Sensor (included)
Temperature Measurement Accuracy
+/- 1 degC
Relays
CH1, CH2 (NC); CH3, CH4 (NO) = 10A 30VDC, 125-250VAC
Relay Control
CH1, CH2, CH3, CH4 = Manual or Automatic based on Volts, Amps, Temperature, Ping(5 secs Interval, 3 min Holdoff) or Time
Power Requirements
10-57VDC Wire Terminal or 802.3af/at Class 0 PoE or 24V Passive PoE
1.5W All Relays Off, 3.5W All Relays On
Accessibility
Via Web Browser and SNMP
Data-Logger
FIFO, Max 4048 data sets, Programmable log interval
Data Connections
8 Pin RJ45, 6pin RJ12 RS232/485 Interface to Tycon MPPT Solar Controllers
Measurement Connections
Removable Wire Terminal
Wire Size
12AWG Max
Mounting
DIN Rail
MTBF
111,199 hrs
Operating Temperature
-40C to +75C (-40F to 167F)
Humidity (RH)
0% - 90%
Dimensions (LxWxH)
125 x 102 x 46mm (4.9” x 4” x 1.8”)
Weight
410g (14.5 oz)
Certifications
FCC & CE
Warranty
3 Years